Heat pump / Cycle lab

Air-source · Vapor compression

Evaporate → Compress → Condense → Expand
Heating mode
Low pressure High pressure
Drag to orbit · Scroll to zoom

Playback

The refrigerant cycle

Display

How the instruments work

The sliders set the outdoor and indoor air temperatures of a steady-state, air-to-air R32 heat pump in heating mode. Each callout shows the refrigerant temperature leaving that component.

Coil temperatures

The refrigerant evaporates 6 °C below outdoor air and condenses 17 °C above room air. The outdoor coil provides 5 °C of superheat and the indoor coil provides 3 °C of subcooling. Liquid expands through the valve at constant enthalpy.

Heating COP

Heating COP is indoor coil heat output divided by total electrical input. The model assumes 1.00 kW of compressor work, 70% isentropic efficiency and 0.10 kW of fan power. Fan heat, defrost and cycling losses are excluded. Actual equipment performance varies.

Stage temperatures and heating output use an offline table calculated for every selectable temperature pair. R32 properties · CoolProp ↗